SECTION 6 ADVANCED SETUP
OMM-139_E 8/25/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 130 of 196
Cascade Configuration). If the unit is configured as a BST Manager, the parameters apply to
this unit and all BST Client units.
1. Go to: Main Menu Advanced Setup BST Cascade Operating Controls.
Figure 6.3.4: BST Cascade: Operating Controls Screen
Sequencing Controls
The Sequencing Controls screen offers options related to sequencing of units in the plant.
NOTES:
This screen is available only after BST Cascade functionality has been enabled (see the
Unit Mode parameter in Section 6.3.1: Cascade Configuration). If the unit is configured
as a BST Manager, the parameters apply to this unit and all BST Client units. If the unit
is configured as a BST Client, the parameters configured on the BST Manager will take
precedence.
The parameters that appear on this screen depend on the Application chosen in
Section 6.3.3: BST Application Configuration.
1. Go to: Main Menu Advanced Setup BST Cascade Operating Controls
Sequencing Controls.
Figure 6.3.4.1: Operating Controls: Sequencing Controls Screen
2. The parameters that appear on this screen depend which Application is chosen in
Section 6.3.3: BST Application Configuration and whether the unit is configured as a BST