6. If you chose Modbus TCP, the BAS Modbus TCP Settings screen appears. Fill in the
parameters to establish communications with BAS via Modbus TCP. Pressing Next
completes the setup (see next step).
Figure 2.4-5: BAS Modbus TCP Settings Screen
7. Once the setup has been configured, the EZ Setup Complete screen displays a summary
of the completed setup as verification that the setup is complete and saved.
STANDALONE UNIT BST MANAGER, APPLICATION =SH & DHW
Figure 2.4-6: Example EZ Setup Complete Screens
2.5 EZ Setup Restoring a Previous Setup
Complete the instructions below if a setup has already been run on the current unit, or on a
different unit and saved to a USB device, and you wish to load that setup on the current unit.
For instructions on saving a setup, see Section 6.1.3: Save and Transfer Settings.
WARNING:
If you are transferring to/from Client or Manager units in a BST Cascade, note the following:
Client and Manager units use separate setup files; Client units require a Client setup file,
and Manager units require a Manager setup file.
If loading the setup from a USB device, the device can have only Client or Manager
setup files but cannot have both on the same device.
If loading the setup from a USB device, the device can have multiple Client files or
multiple Manager (but not both, as started above). The system will automatically load the
file with the latest date for the particular model (you will not have a choice).