TABLE 10-2: Edge Controller O2 Trim Messages
Sensor auto calibration offset required is more
than ±3%
O2 Warning Service Required
Appears if the O
2
level is outside of its limits for
more than 5 minutes.
OnAER Communication failed
The O2 % has gone below 2% for more than 30
seconds
Occurs if O
2
Levels are less than -4% or more
than 24% for more than 10 seconds.
O
2
Levels > 9% and < 24% for more than 30
seconds {auto-reset when value comes back in
range}
10.3 BST CASCADE MESSAGES
The Edge Controller displays the following messages related to Boiler Sequencing Technology
(BST):
TABLE 10-3: Edge Controller BST Cascade Messages