Edge [ii] Controller Operation Manual
SECTION 6 – ADVANCED SETUP
OMM-139_E • 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 137 of 196
1. Go to: Main Menu → Advanced Setup → BST Cascade → Operating Controls →
Setpoint Range. The parameters that appear on this screen depend which Application is
chosen in Section 6.3.3: BST Application Configuration, as shown in the table below.
Application = SH (Space Heating) Application = SH+DHW-Stpt Prty
Figure 6.3.4.6: Operating Controls: Setpoint Range Screen
TABLE 6.13: Setpoint Range Parameters
Other SH PRI Setpt Low Limit
Other SH PRI Setpt Hi Limit
Other DHW PRI Setpt Low Limit
Other DHW PRI Setpt Hi Limit
2. Configure the Setpt Low Limit and Setpt High Limit parameters. Together these two
parameters determine the temperature range within which the setpoint for the chosen
Application can vary. (Range: 60°F to 245°F)
3. Set the Setpoint Limiting parameter to Enabled to Disabled. If Enabled, this feature
acts as a temperature limiting governor. Should a unit’s outlet temperature equal Setpoint
High Limit, a PID function will intervene and maintain the outlet temperature at the Setpoint
High Limit minus the Setpoint Limit Band. If Enabled, the following parameter appears: