Edge [ii] Controller Operation Manual
SECTION 6 ADVANCED SETUP
OMM-139_E 8/25/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 137 of 196
1. Go to: Main Menu Advanced Setup BST Cascade Operating Controls
Setpoint Range. The parameters that appear on this screen depend which Application is
chosen in Section 6.3.3: BST Application Configuration, as shown in the table below.
Application = SH (Space Heating) Application = SH+DHW-Stpt Prty
Figure 6.3.4.6: Operating Controls: Setpoint Range Screen
TABLE 6.13: Setpoint Range Parameters
Available Parameters
Applications
SH
DHW
Other
SH+DH
W-2-Vlv
SH+DH
W-1-Vlv
SH+DH
W-Stpt
Prty
Other+SH-
Stpt Prty
Other+DHW
-Stpt Prty
SH Setpt Low Limit
SH Setpt Hi Limit
DHW Setpt Low Limit
DHW Setpt Hi Limit
Other Setpt Low Limit
Other Setpt Hi Limit
Other SH PRI Setpt Low Limit
Other SH PRI Setpt Hi Limit
Other DHW PRI Setpt Low Limit
Other DHW PRI Setpt Hi Limit
Setpoint Limiting
Setpoint Limit Band
Setback Schedule
Setback Setpoint
Setback Start Time
Setback Stop Time
2. Configure the Setpt Low Limit and Setpt High Limit parameters. Together these two
parameters determine the temperature range within which the setpoint for the chosen
Application can vary. (Range: 60°F to 245°F)
3. Set the Setpoint Limiting parameter to Enabled to Disabled. If Enabled, this feature
acts as a temperature limiting governor. Should a unit’s outlet temperature equal Setpoint
High Limit, a PID function will intervene and maintain the outlet temperature at the Setpoint
High Limit minus the Setpoint Limit Band. If Enabled, the following parameter appears: