EasyManuals Logo

Watts AERCO Edge [ii] User Manual

Watts AERCO Edge [ii]
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #159 background imageLoading...
Page #159 background image
Edge [ii] Controller Operation Manual
SECTION 6 ADVANCED SETUP
OMM-139_E 8/25/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 159 of 196
1. Go to: Main Menu Advanced Setup Performance AERtrim AERtrim Status.
Figure 6.6.1.3: AERtrim: AERtrim Status
2. This screen displays the following “read only” parameters:
Auto Calibration Status: The current Auto Calibration status.
Current Valve Position: The A/F Valves actual current position.
Target Valve Position: The A/F Valves target position.
O2: The current O
2
level.
Current Blower Voltage: The current blower voltage.
Target Blower Voltage: The target voltage
Sensor Status: The current status of the O
2
Sensor.
O2 Timer: The current step in the AERtrim cycle.
3. Set the O2 Monitoring parameter to Yes or No. Yes enables the AERtrim function. When
set to Yes, the O
2
sensor is activated for 4 hours, followed by a 10 hours off period.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watts AERCO Edge [ii] and is the answer not in the manual?

Watts AERCO Edge [ii] Specifications

General IconGeneral
BrandWatts
ModelAERCO Edge [ii]
CategoryController
LanguageEnglish

Related product manuals