Edge [ii] Controller Operation Manual
SECTION 6 ADVANCED SETUP
OMM-139_E 8/25/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 159 of 196
1. Go to: Main Menu Advanced Setup Performance AERtrim AERtrim Status.
Figure 6.6.1.3: AERtrim: AERtrim Status
2. This screen displays the following “read only” parameters:
Auto Calibration Status: The current Auto Calibration status.
Current Valve Position: The A/F Valves actual current position.
Target Valve Position: The A/F Valves target position.
O2: The current O
2
level.
Current Blower Voltage: The current blower voltage.
Target Blower Voltage: The target voltage
Sensor Status: The current status of the O
2
Sensor.
O2 Timer: The current step in the AERtrim cycle.
3. Set the O2 Monitoring parameter to Yes or No. Yes enables the AERtrim function. When
set to Yes, the O
2
sensor is activated for 4 hours, followed by a 10 hours off period.