6. If you chose Remote Setpoint in step 4, the Select Remote Setpoint Type screen
appears. Choose how the unit will access the setpoint, then press Next.
Figure 2.3.2.2.2-8: BST Manager – DHW & Other: Select Remote Setpoint Type
A. If you chose either 4-20mA or 0-20mA, the Other Analog Input screen appears.
Configure the following parameters. Pressing Next takes you to the Select BAS
Mode screen; skip to Section 2.4: Completing the Installation for instructions.
• Choose the remote setpoint source in the Other Rmt Setpt Source field (a
green border appears on the previous choice, if there was one): Spare Analog
in 1, Spare Analog in 2, Spare Analog in 3.
• Enter the upper and lower limits of the “other” setpoint in the BST Other
Setpt Lo Limit and BST Other Setpt Hi Limit fields.
• Pressing Next takes you to the Select BAS Mode screen; skip to Section 2.4:
Completing the Installation for instructions.
Figure 2.3.2.2.2-9: BST Manager – DHW & Other: Other Analog Input Screen
B. If you chose Network, the Select BAS Mode screen. Skip to Section 2.4:
Completing the Installation for instructions.