Manual 37128A GCP-20 Series - Genset Control
Page 184/190 © Woodward
Option
Parameter
1. Line Text 2. Line
Adjustment range Standard setting Customer settings
Code
level
C
ONFIGURATION OF THE ENGINE
Configure engine
YES/NO YES Y N Y N 2
Aux. services prerun
0 to 999 s 0 s 2
Aux. services postrun
0 to 999 s 0 s 2
Start-Stop-Logic for
DIESEL/GAS Diesel 2
min. speed for
0 to 999 rpm 100 rpm 2
Gas
Ignition delay
1 to 99 s 3 s 2
..
Gasvalve Delay
1 to 99 s 5 s 2
..
Starter time
2 to 99 s 5 s 2
..
Start pause time
1 to 99 s 8 s 2
..
freq. low before start
ON/OFF OFF o c o c 2
Gas
action time for freq. low
0 to 999 s 5 s 2
Diesel
Preglow time
0 to 99 s 3 s 2
..
Starter time
2 to 99 s 5 s 2
..
Start pause time
1 to 99 s 8 s 2
..
freq. low before start
ON/OFF OFF o c o c 2
..
action time for freq. low
0 to 999 s 5 s 2
Diesel
Start-Stop-Logic
open/close to stop close to stop o c o c 2
Cooldown time
0 to 999 s 30 s 2
firing speed by Term. 62
ON/OFF OFF on off on off 2
Delayed engine monitoring
1 to 99 s 8 s 2
Firing speed reached: f>
15 to 70 Hz 2
Pickup input
ON/OFF OFF on off on off 2
nominal speed Gen. 1/min
1,000 to 2,000 rpm 1,500 rpm 2
Number of pickup teeth
30 to 280 96 2
COUNTER CONFIGURATION
Configure Counter
YES/NO Yes Y N Y N 2
Service Interval in
0 to 99,999 h 300 h 1
Set oper.hours counter
0 to 65,000 h 0 h 2
Start counter set
0 to 32,749 0 2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Woodward GCP-20 Series and is the answer not in the manual?

Woodward GCP-20 Series Specifications

General IconGeneral
BrandWoodward
ModelGCP-20 Series
CategoryControl Unit
LanguageEnglish

Related product manuals