Troubleshooting
7
7.4 Fault
YASKAWA SIEPYEULA5001C LA500 Technical Manual 183
Code Name Causes Possible Solutions
Uv3 Soft Charge Answerback Fault
There is damage to the relay or contactor on the
soft-charge bypass relay.
• Re-energize the drive.
• If the fault stays, replace the control board or the drive.
• Monitor U4-06 [PreChargeRelayMainte] shows the
performance life of the soft-charge bypass relay. If U4-06 is
more than 90%, replace the board or the drive. For information
about replacing the control board, contact Yaskawa or your
nearest sales representative.
Air inside the drive is too hot. Decrease the ambient temperature of the drive.
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.