Electrical Installation
3
3.12 Prevent Switching Surge
YASKAWA SIEPYEULA5001C LA500 Technical Manual 71
3.12 Prevent Switching Surge
Connect a Surge Protective Device
A surge protective device decreases the surge voltage generated when you switch an inductive load near the drive.
Inductive loads include:
Magnetic contactors
Electromagnetic relays
Magnetic valves
Solenoids
Magnetic brakes.
Always use a surge protective device or diode with inductive loads.
Note:
Do not connect a surge protective device to the drive output side.