11.16 Defaults by Drive Model
278 YASKAWA SIEPYEULA5001C LA500 Technical Manual
11.16 Defaults by Drive Model
The values for the parameters in these tables depend on the values for parameter o2-04. Changing the settings for
o2-04 will change the default settings.
Three-Phase 200 V Class
Parameter Name Unit Default
- Drive Model - 2018 2025 2033 2047 2060 2075
o2-04 Drive Model Selection Hex. 68 6A 6B 6D 6E 6F
E2-11 Motor Rated Power kW 3.7 5.5 7.5 11 15 18.5
C6-02 Carrier Frequency Selection - 3 3 3 3 3 3
E2-01 Motor Rated Current (FLA) A 14 19.6 26.6 39.7 53 65.8
E2-02 Motor Rated Slip Hz 2.73 1.5 1.3 1.7 1.6 1.67
E2-03 Motor No-Load Current A 4.5 5.1 8 11.2 15.2 15.7
E2-05 Motor Line-to-Line Resistance Ω 0.771 0.399 0.288 0.23 0.138 0.101
E2-06 Motor Leakage Inductance % 19.6 18.2 15.5 19.5 17.2 20.1
E2-10 Motor Iron Loss W 112 172 262 245 272 505
L2-05
Undervoltage Detection Lvl
(Uv1)
- 190 190 190 190 190 190
L8-02 Overheat Alarm Level °C 115 105 115 125 120 135
L8-09
Output Ground Fault
Detection
- 0 1 1 1 1 1
L8-38 Carrier Frequency Reduction - 1 2 2 2 2 2
T1-02 Motor Rated Power kW 3.7 5.5 7.5 11 15 18.5
T1-04 Motor Rated Current A 14 19.6 26.6 39.7 53 65.8
Three-Phase 400 V Class
Parameter Name Unit Default
- Drive Model - 4009 4015 4018 4024 4031 4039 4060
o2-04 Drive Model Selection Hex. 72 73 74 75 76 77 78
E2-11 Motor Rated Power kW 4.0 5.5 7.5 11 15 18.5 22
C6-02 Carrier Frequency Selection - 3 3 3 3 3 3 3
E2-01 Motor Rated Current (FLA) A 7 9.8 13.3 19.9 26.5 32.9 38.6
E2-02 Motor Rated Slip Hz 2.7 1.5 1.3 1.7 1.6 1.67 1.7
E2-03 Motor No-Load Current A 2.3 2.6 4 5.6 7.6 7.8 9.2
E2-05 Motor Line-to-Line Resistance Ω 3.333 1.595 1.152 0.922 0.55 0.403 0.316
E2-06 Motor Leakage Inductance % 19.3 18.2 15.5 19.6 17.2 20.1 23.5
E2-10 Motor Iron Loss W 130 193 263 385 440 508 586
L2-05
Undervoltage Detection Lvl
(Uv1)
- 380 380 380 380 380 380 380
L8-02 Overheat Alarm Level °C 110 120 120 120 120 125 115
L8-09
Output Ground Fault
Detection
- 0 0 0 1 1 1 1
L8-38 Carrier Frequency Reduction - 1 2 2 2 2 2 2
T1-02 Motor Rated Power kW 4.0 5.5 7.5 11 15 18.5 22
T1-04 Motor Rated Current A 7 9.8 13.3 19.9 26.5 32.9 38.6