11.8 H: Terminal Functions
250 YASKAWA SIEPYEULA5001C LA500 Technical Manual
Setting Value Function Description Ref.
41 Reverse RUN (2-Wire)
Sets the Forward Run command for 2-wire sequence 1. Set this function and H1-xx = 40 [Forward RUN (2-Wire)]
together.
ON : Reverse Run
OFF : Stop
Note:
If you turn ON the Forward Run command terminal and the Reverse Run command terminal, it will cause an
EF [FWD/REV Run Command Input Error] alarm and the motor will ramp to stop.
Initialize the drive with a 2-wire sequence to set the Reverse Run command to terminal S2.
This function will not operate at the same time as H1-xx = 42, 43 [Run Command (2-Wire Sequence 2),
FWD/REV (2-Wire Sequence 2)].
309
50 Nominal Speed
Sets the speed reference nominal speed.
309
51 Intermed Speed
Sets the speed reference intermediate speed 1. In combination with nominal and releveling speed you can set
intermediate speed 2 and 3.
309
52 Releveling Speed
Sets the speed reference releveling speed.
309
53 Leveling Speed
Sets the speed reference leveling speed.
309
54 Inspection Speed
Sets the speed reference inspection speed.
309
55 Rescue Operation
Activates rescue operation.
309
56 Motor Contractor
Feedback
Used for motor contactor supervision and fault detection.
310
79 Brake Feedback
Used for brake supervision and detection of incorrect operation.
310
H2: Digital Outputs
No.
(Hex.)
Name Description
Default
(Range)
Ref.
H2-01
(040B)
Term MA/MB-MC
Function Selection
Sets the function set for MFDO terminal MA-MC or MB-MC.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in
through mode.
E
(0 - 158)
311
H2-02
(040C)
Term P1-C1 Function
Selection
Sets the function for MFDO terminal P1-C1.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in
through mode.
6
(0 - 158)
311
H2-03
(040D)
Term P2-C2 Function
Selection
Sets the function for MFDO terminal P2-C2.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in
through mode.
50
(0 - 158)
311
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV

Table of Contents

Other manuals for YASKAWA LA500

Related product manuals