2.3 Installation Position and Clearances
28 YASKAWA SIEPYEULA5001C LA500 Technical Manual
2.3 Installation Position and Clearances
Install the drive as shown in Figure 2.1 for sufficient airflow to cool the drive.
A - Vertical installation
B - Horizontal installation
C - Rotated installation
Figure 2.1 Installation Orientation
Install Single Drive
Use the clearances specified in Figure 2.2 to install the drive. Make sure that there is sufficient space for wiring
and airflow.
A - 50 mm (2 in) minimum
B - 30 mm (1.18 in) minimum on each side
C - 100 mm (3.94 in) minimum above and below
D - Airflow direction
Figure 2.2 Installation Clearances for One Drive
Install the Drive Horizontally
When you install drives horizontally, set L8-12 = 40 [Ambient Temperature Setting = 40 °C] and L8-35 = 1
[Installation Method Selection = Side-by-Side Mounting]. Use the clearances specified in Figure 2.4 and Figure
2.5 to install the drive. Make sure that there is sufficient space for wiring and airflow. To install the drive model
4009 horizontally, install an external cooling fan. Refer to Table 2.1 for more information about the external
cooling fan.

Table of Contents

Other manuals for YASKAWA LA500