Standards Compliance
5
5.2 European Standards
YASKAWA SIEPYEULA5001C LA500 Technical Manual 119
EMC Directive
Use drives with built-in EMC filters or install external EMC filters to the drive input side to comply with the
EMC Directive.
Drives with built-in EMC filters (models 2xxxE, 4xxxE) were tested in accordance with European standard EN
61800-3, and comply with the EMC Directive.
Install a Drive to Conform to the EMC Directive
Install drive models 2xxxE, and 4xxxE with this procedure to comply with the EMC Directive when the drive is a
single unit or installed in a larger device.
1. Install the drive on a grounded metal plate.
2. Wire the drive and motor.
3. Ground the wire shielding on the drive side and motor side.
A - Drive
B - Wiring length
*1
C - Motor
D - Metal conduit
E - Grounding wire
Figure 5.4 Wiring the Drive and Motor
*1 The maximum wiring length between the drive and motor is:
2xxxE, 4xxxE: 20 m (65.6 ft)
Note:
Use a braided shield cable for the drive and motor wiring or put the wires through a metal conduit.
Keep the cable between the drive and motor and the grounding wire as short as possible.
4. Use a cable clamp to ground the motor cable to the metal plate.
Note:
Make sure that the protective ground wire complies with technical specifications or local safety standards.
A - Braided shield cable
B - Metal plate
C - Cable clamp (conductive)
Figure 5.5 Ground the Shield