12.8 n: Special Adjustment
346 YASKAWA SIEPYEULA5001C LA500 Technical Manual
Note:
Set n2-02 n2-03. If n2-02 > n2-03, the drive will detect oPE08 [Parameter Selection Error].
n6: Online Tuning
n6 parameters are used to set the online tuning function for motor line-to-line resistance.
The Online Tuning for motor line-to-line resistance is used to prevent degradation of speed control accuracy due
to motor temperature fluctuation and motor stalls due to insufficient torque.
n6-01: Online Tuning Selection
No.
(Hex.)
Name Description
Default
(Range)
n6-01
(0570)
Expert
Online Tuning Selection
Sets the type of motor data that Online Tuning uses for OLV control.
1
(0 - 2)
0 : Disabled
1 : Line-to-Line Resistance Tuning
The drive adjusts the motor line-to-line resistance during run. This procedure is applicable for speed values 6 Hz
and less. It also adjusts the motor resistance value to increase the overload capacity in the low speed range.
2 : Voltage Correction Tuning
The drive adjusts the output voltage during run to increase overload tolerance and minimize the effects of high
temperatures on speed precision.
Note:
Setting 2 is enabled only when b8-01 = 0 [Energy Saving Control Selection = Disabled].
V/f
OLV