Parameter Details
12
12.6 H: Terminal Function Selection
YASKAWA SIEPYEULA5001C LA500 Technical Manual 311
■ H2-01: Term MA/MB-MC Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-01
(040B)
Term MA/MB-MC
Function Selection
Sets the function set for MFDO terminal MA-MC or MB-MC.
E
(0 - 158)
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in through mode.
■ H2-02: Term P1-C1 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-02
(040C)
Term P1-C1 Function
Selection
Sets the function for MFDO terminal P1-C1.
6
(0 - 158)
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in through mode.
■ H2-03: Term P2-C2 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-03
(040D)
Term P2-C2 Function
Selection
Sets the function for MFDO terminal P2-C2.
50
(0 - 158)
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in through mode.
◆ MFDO Setting Values
Selects the function configured to MFDO.
■ 0: During Run
Setting Value Function Description
0 During Run
The terminal activates when you input a Run command and when the drive is outputting voltage.
Figure 12.10 Drive Running Time Chart
ON : Drive is running
The drive is receiving a Run command or outputting voltage.
OFF : Drive is stopping
■ 1: Zero Speed
Setting Value Function Description
1 Zero Speed
The terminal activates when the output frequency is less than E1-09 [Minimum Output Frequency] or b2-01 [DC Injection/Zero
SpeedThreshold].