11.3 A: Initialization Parameters
238 YASKAWA SIEPYEULA5001C LA500 Technical Manual
11.3 A: Initialization Parameters
◆ A1: Initialization
No.
(Hex.)
Name Description
Default
(Range)
Ref.
A1-00
(0100)
RUN
Language Selection
Sets the language for the LCD keypad.
Note:
• When you use A1-03 [Initialize Parameters] to initialize the drive, the drive will
not reset this parameter.
0 : English
1 : Japanese
2 : German
3 : French
4 : Italian
5 : Spanish
6 : Portuguese
7 : Chinese
8 : Czech
9 : Russian
10 : Turkish
11 : Polish
12 : Greek
0
(0 - 12)
280
A1-01
(0101)
RUN
Access Level Selection
Sets user access to parameters. The access level controls which parameters the keypad
will display, and which parameters the user can set.
0 : Operation Only
1 : User Parameters
2 : Advanced Level
3 : Expert Level
2
(0 - 3)
280
A1-02
(0102)
Control Method
Selection
Sets the control method for the drive application and the motor.
0 : V/f Control
2 : Open Loop Vector
0
(0, 2)
281
A1-03
(0103)
Initialize Parameters
Sets parameters to default values.
0 : No Initialization
1110 : User Initialization
2220 : 2-Wire Initialization
0
(0 - 2220)
281
A1-04
(0104)
Password
Entry point for the password set in A1-05 [Password Setting]. The user can view the
settings of parameters that are locked without entering the password. Enter the correct
password in this parameter to change parameter settings.
0000
(0000 - 9999)
282
A1-05
(0105)
Password Setting
Set the password to lock parameters and prevent changes to parameter settings. Enter
the correct password in A1-04 [Password] to unlock parameters and accept changes.
0000
(0000 - 9999)
282
◆ A2: User Parameters
No.
(Hex.)
Name Description
Default
(Setting Range)
Ref.
A2-01
(0106)
User Parameter 1
Sets the parameter number to show on the first line in Setup Mode. You can select a
maximum of 32 parameters for the drive and set them to parameters A2-01 to A2-32.
A1-00 283
A2-02
(0107)
User Parameter 2
Sets the parameter number to show on the second line in Setup Mode. You can select a
maximum of 32 parameters for the drive and set them to parameters A2-01 to A2-32.
A1-02 283
A2-03
(0108)
User Parameter 3
Sets the parameter number to show on the third line in Setup Mode. You can select a
maximum of 32 parameters for the drive and set them to parameters A2-01 to A2-32.
d1-18 283
A2-04
(0109)
User Parameter 4
Sets the parameter number to show on the fourth line in Setup Mode. You can select a
maximum of 32 parameters for the drive and set them to parameters A2-01 to A2-32.
d1-19 283
A2-05
(010A)
User Parameter 5
Sets the parameter number to show on the fifth line in Setup Mode. You can select a
maximum of 32 parameters for the drive and set them to parameters A2-01 to A2-32.
d1-23 283