Parameter Details
12
12.7 L: Protection Functions
YASKAWA SIEPYEULA5001C LA500 Technical Manual 329
L1-02: Motor Overload Protection Time
No.
(Hex.)
Name Description
Default
(Range)
L1-02
(0481)
Expert
Motor Overload Protection
Time
Sets the operation time for the electronic thermal protector of the drive to prevent damage to the
motor. Usually it is not necessary to change this setting.
1.0 min
(0.1 - 5.0 min)
Set the overload tolerance time to the length of time that the motor can operate at 150% load from continuous
operation at 100% load.
When the motor operates at 150% load continuously for 1 minute after continuous operation at 100% load (hot
start), the default setting triggers the electronic thermal protector.
Figure 12.27 shows an example of the electronic thermal protector operation time. Motor overload protection
operates in the range between a cold start and a hot start.
This example shows a general-purpose motor operating at the base frequency with L1-02 set to 1.0 min.
Cold start
Shows the motor protection operation time characteristics when the overload occurs immediately after starting
operation from a complete stop.
Hot start
Shows the motor protection operation time characteristics when overload occurs from continuous operation
below the motor rated current.
Figure 12.27 Protection Operation Time for a General-purpose Motor at Rated Output Frequency
L1-13: Motor Overload Memory Selection
No.
(Hex.)
Name Description
Default
(Range)
L1-13
(046D)
Expert
Motor Overload Memory
Selection
Sets the function that keeps the current electronic thermal protector value when the drive stops
receiving power.
1
(0, 1)
0 : Disabled
1 : Enabled
Sets if the drive will calculate the motor again when the drive is energized again.
L2: Power Loss Ride Through (Undervoltage Detection)
L2-05: Undervoltage Detection Lvl (Uv1)
No.
(Hex.)
Name Description
Default
(Range)
L2-05
(0489)
Expert
Undervoltage Detection Lvl
(Uv1)
Sets the voltage at which a Uv1 [DC Bus Undervoltage] fault is triggered. Usually it is not
necessary to change this setting.
Determined by E1-01
(400 V Class: 300 - 420 V)
NOTICE: Damage to Equipment. When you set this parameter to a value lower than the default, you must install an AC reactor
on the input side of the power supply. If you do not install an AC reactor, it will cause damage to the drive circuitry.
V/f
OLV
V/f
OLV
V/f
OLV