Parameter Details
12
12.6 H: Terminal Function Selection
YASKAWA SIEPYEULA5001C LA500 Technical Manual 309
Figure 12.9 2-Wire Sequence Wiring Example
41: Reverse RUN (2-Wire)
Setting Value Function Description
41 Reverse RUN (2-Wire)
Sets the Forward Run command for 2-wire sequence 1. Set this function and H1-xx = 40 [Forward RUN (2-Wire)] together.
ON : Reverse Run
OFF : Stop
Note:
If you turn ON the Forward Run command terminal and the Reverse Run command terminal, it will cause an EF [FWD/REV Run
Command Input Error] alarm and the motor will ramp to stop.
Initialize the drive with a 2-wire sequence to set the Reverse Run command to terminal S2.
This function will not operate at the same time as H1-xx = 42, 43 [Run Command (2-Wire Sequence 2), FWD/REV (2-Wire Sequence
2)].
50: Nominal Speed
Setting Value Function Description
50 Nominal Speed
Sets the speed reference nominal speed.
51: Intermed Speed
Setting Value Function Description
51 Intermed Speed
Sets the speed reference intermediate speed 1. In combination with nominal and releveling speed you can set intermediate speed
2 and 3.
52: Releveling Speed
Setting Value Function Description
52 Releveling Speed
Sets the speed reference releveling speed.
53: Leveling Speed
Setting Value Function Description
53 Leveling Speed
Sets the speed reference leveling speed.
54: Inspection Speed
Setting Value Function Description
54 Inspection Speed
Sets the speed reference inspection speed.
55: Rescue Operation
Setting Value Function Description
55 Rescue Operation
Activates rescue operation.
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV