Parameter List
11
11.8 H: Terminal Functions
YASKAWA SIEPYEULA5001C LA500 Technical Manual 249
Setting Value Function Description Ref.
22 External Fault (NO-
@Run-Ramp)
When the terminal activates during run, the drive ramps to stop in the selected deceleration time. Fault relay output
terminal MA-MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while the
drive is stopped.
307
23 External Fault (NC-
@Run-Ramp)
When the terminal deactivates during run, the drive ramps to stop in the selected deceleration time. Fault relay
output terminal MA-MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while
the drive is stopped.
307
24 External Fault (NO-
Always-Coast)
When the terminal activates, the drive shuts off the output and the motor coasts to stop. Fault relay output terminal
MA-MC will turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is
stopped or running.
307
25 External Fault (NC-
Always-Coast)
When the terminal deactivates, the drive shuts off the output and the motor coasts to stop. Fault relay output
terminal MA-MC will turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the
drive is stopped or running.
307
26 External Fault (NO-
@Run-Coast)
When the terminal activates during run, the drive shuts off the output and the motor coasts to stop. Fault relay
output terminal MA-MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while
the drive is stopped.
307
27 External Fault (NC-
@Run-Coast)
When the terminal deactivates during run, the drive shuts off the output and the motor coasts to stop. Fault relay
output terminal MA-MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while
the drive is stopped.
307
28 External Fault (NO-
Always-FStop)
When the terminal activates, the drive stops the motor in the deceleration time set to C1-09 [Fast Stop Time]. Fault
relay output terminal MA-MC turns ON, and MB-MC turns OFF. Stopped drives and running drives will detect
external faults.
307
29 External Fault (NC-
Always-FStop)
When the terminal deactivates, the drive stops the motor in the deceleration time set to C1-09 [Fast Stop Time].
Fault relay output terminal MA-MC turns ON, and MB-MC turns OFF. Stopped drives and running drives will
detect external faults.
307
2A External Fault (NO-
@Run-FStop)
When the terminal activates during run, the drive stops the motor in the deceleration time set to C1-09 [Fast Stop
Time]. Fault relay output terminal MA-MC turns ON, and MB-MC turns OFF. Stopped drives will not detect
external faults.
307
2B External Fault (NC-
@Run-FStop)
When the terminal deactivates during run, the drive stops the motor in the deceleration time set to C1-09 [Fast
Stop Time]. Fault relay output terminal MA-MC turns ON, and MB-MC turns OFF. Stopped drives will not detect
external faults.
307
2C External Fault (NO-
Always-Alarm)
When the terminal activates, the keypad shows EFx [External Fault (Input Terminal Sx)] and the output terminal
set for Alarm [H2-01 to H2-03 = 10] activates. The drive continues operation. Stopped drives and running drives
will detect external faults.
307
2D External Fault (NC-
Always-Alarm)
When the terminal deactivates, the keypad shows EFx [External Fault (Input Terminal Sx)] and the output terminal
set for Alarm [H2-01 to H2-03 = 10] activates. The drive continues operation. Stopped drives and running drives
will detect external faults.
307
2E External Fault (NO-
@Run-Alarm)
When the terminal activates during run, the keypad shows EFx [External Fault (Input Terminal Sx)] and the output
terminal set for Alarm [H2-01 to H2-03 = 10] activates. The drive continues operation. Stopped drives will not
detect external faults.
307
2F External Fault (NC-
@Run-Alarm)
When the terminal deactivates during run, the keypad shows EFx [External Fault (Input Terminal Sx)] and the
output terminal set for Alarm [H2-01 to H2-03 = 10] activates. The drive continues operation. Stopped drives will
not detect external faults.
307
40 Forward RUN (2-Wire)
Sets the Forward Run command for 2-wire sequence 1. Set this function and H1-xx = 41 [Reverse RUN (2-Wire)]
together.
ON : Forward Run
OFF : Stop
Note:
• If you turn ON the Forward Run command terminal and the Reverse Run command terminal, it will cause an
EF [FWD/REV Run Command Input Error] alarm and the motor will ramp to stop.
• Initialize the drive with a 2-wire sequence to set the Forward Run command to terminal S1.
• This function will not operate at the same time as H1-xx = 42, 43 [Run Command (2-Wire Sequence 2),
FWD/REV (2-Wire Sequence 2)].
308