Troubleshooting
7
7.5 Minor Faults/Alarms
YASKAWA SIEPYEULA5001C LA500 Technical Manual 187
Code Name Causes Possible Solutions
The internal cooling fan or fans have stopped. 1. Use the procedures in this manual to replace the cooling fan.
2. Set o4-03 = 0 [Fan Operation Time Setting = 0 h].
Note:
The drive detects this error if the heatsink temperature of the drive is more than L8-02.
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
If the drive detects this error, it will operate the motor as specified by the stopping method set in L8-03 [Overheat Pre-Alarm Selection].
Code Name Causes Possible Solutions
oH2 External Overheat (H1-XX=B)
An external device sent an oH2. 1. Find the external device that output the overheat alarm.
2. Remove the cause of the problem.
3. Clear the Overheat Alarm (oH2) [H1-xx = B] set to MFDI
terminals S1 to S7.
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Code Name Causes Possible Solutions
oL3 Overtorque 1
A fault occurred on the machine.
Example: The machine is locked.
Examine the machine and remove the cause of the fault
The parameters are incorrect for the load. Adjust L6-02 [Torque Detection Level 1] and L6-03 [Torque
Detection Time 1].
Note:
The drive detects this fault if the drive output current is more than the level set in L6-02 for longer than L6-03.
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Set the conditions that trigger the minor fault using L6-01 [Torque Detection Selection 1].
Code Name Causes Possible Solutions
oL4 Overtorque 2
A fault occurred on the machine.
Example: The machine is locked.
Examine the machine and remove the cause of the fault
The parameters are incorrect for the load. Adjust L6-05 [Torque Detection Level 2] and L6-06 [Torque
Detection Time 2].
Note:
The drive detects this error if the drive output current is more than the level set in L6-05 for longer than L6-06.
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Set the conditions that trigger the minor fault using L6-04 [Torque Detection Selection 2].
Code Name Causes Possible Solutions
ov Overvoltage
There are surge voltages in the input power supply. Connect a DC reactor to the drive.
Note:
If you turn the phase advancing capacitors ON and OFF and
use thyristor converters in the same power supply system,
there can be surge voltages that irregularly increase the input
voltage.
The drive output cable or motor is shorted to ground
(the current short to ground is charging the main
circuit capacitor of the drive through the power
supply).
1. Examine the motor main circuit cable, terminals, and motor
terminal box, and then remove ground faults.
2. Re-energize the drive.
The power supply voltage is too high. Decrease the power supply voltage to match the drive rated
voltage.
Electrical interference caused a drive malfunction. Examine the control circuit lines, main circuit lines, and
ground wiring, and decrease the effects of electrical
interference.
Make sure that a magnetic contactor is not the source of the
electrical interference, then use a Surge Protective Device if
necessary.
Set L5-01 0 [Number of Auto-Restart Attempts 0 times].
Note:
The drive detects this error if the DC bus voltage is more than the ov detection level when the Run command has not been input (while the drive is stopped).
The ov detection level is approximately 410 V with 200 V class drives. The detection level is approximately 820 V for 400 V class drives.
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Code Name Causes Possible Solutions
ovEr Too Many Parameters Changed
You tried to change more than 150 parameters. Make sure that parameters that do not have an effect on drive
operation are at their default settings.
Note:
You can change 150 parameters maximum.
If you change parameters that have dependencies, the drive
can detect ovEr when the number of changed parameters is
fewer than 150.
Code Name Causes Possible Solutions
PF Input Phase Loss
There is a phase loss in the drive input power. Correct all wiring errors with the main circuit power supply.
Loose wiring in the input power terminals. Tighten the screws to the correct tightening torque.
The drive input power voltage is changing too
much.
Examine the supply voltage for problems.
Make the drive input power stable.