Troubleshooting
7
7.6 Parameter Setting Errors
YASKAWA SIEPYEULA5001C LA500 Technical Manual 191
Code Name Causes Possible Solutions
oPE10 V/f Data Setting Error
The parameters that set the V/f pattern do not
satisfy these conditions:
• For motor 1: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤
E1-04 [Minimum Output Frequency ≤ Mid Point
A Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
• For motor 2: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤
E3-04 [Minimum Output Frequency ≤ Mid Point
A Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
Set the parameters correctly to satisfy the conditions.