12.6 H: Terminal Function Selection
306 YASKAWA SIEPYEULA5001C LA500 Technical Manual
Figure 12.7 Baseblock Command Time Chart
ON : Baseblock (drive output stop)
OFF : Normal operation
9: Baseblock Command (N.C.)
Setting Value Function Description
9 Baseblock Command (N.
C.)
Sets the command that stops drive output and coasts the motor to stop when the input terminal is OFF.
The keypad flashes bb [Baseblock]. If you cancel the baseblock command when the Run command is active, the
drive will restart the motor and use the speed search function.
ON : Normal operation
OFF : Baseblock (drive output stop)
WARNING! Sudden Movement Hazard. When you use a mechanical holding brake with the drive, you must close the brake if
an input terminal triggers the Baseblock command to stop drive output. If you enter the baseblock command, the motor will
suddenly coast and the load will slip, which can cause serious injury or death.
F: Not Used
Setting Value Function Description
F Not Used
Use this setting for unused terminals or to use terminals in through mode.
14: Fault Reset
Setting Value Function Description
14 Fault Reset
Sets the command to reset the current fault when the Run command is inactive.
If the drive detects a fault, the drive will activate the fault relay output, turn off the output, and the motor will
coast to stop.
If the drive detects a fault for which you can set the stopping method, apply the appropriate Stopping Method.
Then push (RESET) on the keypad to turn the Run command OFF, or activate the fault reset terminal to reset
the fault.
Note:
The drive ignores the fault reset command when the Run command is active. Remove the Run command before trying to reset a fault.
15: Fast Stop (N.O.)
Setting Value Function Description
15 Fast Stop (N.O.)
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is ON while
the drive is operating.
If you cancel the fast stop input, the drive will not restart the motor until you meet these conditions:
Fully stop the motor
Cancel the Run command
Cancel the fast stop command
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV