12.6 H: Terminal Function Selection
YASKAWA SIEPYEULA5001C LA500 Technical Manual 321
Figure 12.22 Analog Output Gain/Bias Configuration Example 1
For example, when the parameter value set to analog output is 0, and a 3 V signal is to be output to terminal AM,
set H4-03 [AM Analog Output Bias] = 30%.
Figure 12.23 Analog Output Gain/Bias Configuration Example 2
■ Calibrate Terminal AM
Stop the drive to calibrate meters. Use this procedure to calibrate:
1. Show H4-02 [Terminal AM Analog Output Gain] on the keypad.
Terminal AM outputs the analog signal when the monitor item that you set in H4-01 [Terminal AM Analog
Output Select] is 100%.
2. Adjust H4-02 while referencing the meter scale connected to terminal AM.
3. Show H4-03 [Terminal AM Analog Output Bias] on the keypad.
The analog signal at the time when the monitor item selected with H4-01 is 0% is output from terminal AM.
4. Adjust H4-03 while referencing the meter scale connected to terminal AM.
■ H4-01: Terminal AM Analog Output Select
Set the x-xx part of the Ux-xx [Monitor]. For example, set H4-01 = 102 to monitor U1-02 [Output Frequency].
Note:
• You cannot use all of the monitors in all of the control methods.
■ H4-02: Terminal AM Analog Output Gain
No.
(Hex.)
Name Description
Default
(Range)
H4-02
(041E)
RUN
Expert
Terminal AM Analog
Output Gain
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
100.0%
(-999.9 - +999.9%)
The analog signal output from the AM terminal is a maximum of 10 V (or 20 mA). Use H4-07 [Terminal AM
Signal Level Select] to set the signal level.