Parameter Details
12
12.9 o: Keypad-Related Settings
YASKAWA SIEPYEULA5001C LA500 Technical Manual 349
• o1-10 = 10000
• o1-11 = 2 [User Units Decimal Position = 2 Dec (XXX.XX)]
■ o1-10: User Units Maximum Value
No.
(Hex.)
Name Description
Default
(Range)
o1-10
(0520)
Expert
User Units Maximum Value
Sets the value that the drive shows as the maximum output frequency.
Determined by o1-03
(1 - 60000)
To display a maximum output frequency of 100.00, set parameters to these values:
• o1-10 = 10000
• o1-11 = 2 [User Units Decimal Position = Two Decimal Places (XXX.XX)]
Note:
Set o1-03 = 3 [Frequency Display Unit Selection = User Units (o1-10 & o1-11)] before you set o1-10 and o1-11.
■ o1-11: User Units Decimal Position
No.
(Hex.)
Name Description
Default
(Range)
o1-11
(0521)
Expert
User Units Decimal
Position
Sets the number of decimal places for frequency reference and monitor values.
Determined by o1-03
(0 - 3)
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
Note:
Set o1-03 = 3 [Frequency Display Unit Selection = User Units (o1-10 & o1-11)] before you set o1-10 [User Units Maximum Value] and
o1-11.
■ o1-24 to o1-29: Custom Monitor 1 to 6
No.
(Hex.)
Name Description
Default
(Range)
o1-24 to o1-29:
(11AD - 11B2)
RUN
Custom Monitor 1 to 6
Sets a maximum of 6 monitors as user monitors. This parameter is only available when using an
LCD keypad.
o1-24: 101
o1-25: 102
o1-26: 103
o1-27 to o1-29: 0
(0, 101 - 999)
These parameters save the monitor items selected by the LCD keypad [Custom Monitor].
Note:
• You can show a maximum of three selected monitors on one LCD keypad screen.
–When you select only one monitor, the text size of this monitor increases. For example, when o1-25 to o1-29 = 0, the text size of the
monitor saved in o1-24 increases.
–When you select two monitors, the text size of these monitors increase.
–When you select four or more monitors, the fourth monitor and all additional monitors are shown on the next screens.
• Monitors selected with o1-24 to o1-26 can be displayed as a bar graph, analog gauge, or trend plot.
–Bar graph display: 3 monitors maximum
Select with o1-24, o1-25, and o1-26.
–Analog gauge display: 1 monitor
Select with o1-24.
–Trend plot display: 2 monitors
Select with o1-24 and o1-25.
• You can only set parameters o1-24 to o1-26 with analog output monitors.
• You can set all monitors to parameters o1-27 to o1-29.