2.1 MP3200 Installation
2.1.6 Battery Installation and Replacement
2-18
Battery Replacement
When Using the CPU-201
1.
Back up the programs and data stored in the MP3200.
Note: The backup can be used to recover the data if the data accidentally gets deleted during Battery replace-
ment. Refer to the following section for details on backing up the data.
4.5 Transferring Data with the MPE720 on page 4-65
2.
Confirm that the RDY indicator on the CPU Unit is lit.
3.
Open the battery holder on the bottom of the CPU Unit.
CAUTION
Suitable battery replacement must be performed and it must be performed only by an
experienced technician.
There is a risk of electrical shock, injury, or device damage.
Replace the Battery only while power is supplied to the MP3200.
Replacing the Battery while the power supply to the MP3200 is turned OFF may result in
loss of the data stored in memory in the MP3200.
Do not touch the electrodes when replacing the Battery.
Static electricity may damage the electrodes.
Observe all local laws and ordinances when you dispose of used Batteries.
Lit.
Lit.
Battery holder