Tools Required for Installation
A straight-edge screwdriver (blade depth: 0.4 mm, width: 2.5 mm) is required to install the unit and wire the option terminal
block.
Note: Tools required to prepare option cables for wiring are not listed in this manual.
n
Power Supply Terminal Block TB1 Functions
Figure 3.58 Power Supply Terminal Block TB1
Table 3.25 Power Supply Terminal Block TB1 Functions
Terminal Function
24 +24 Vdc Input
0 0 V
FE Ground
n
Wire Gauges and Tightening Torques
Table 3.26 Wire Gauges and Tightening Torques
Terminal Screw Size
Tightening
Torque Nm
(inlb)
Bare Cable Crimp Terminals
Wire Type
Recomm.
Gauge mm
2
(AWG)
Applicable
Gauges mm
2
(AWG)
Recomm.
Gauge mm
2
(AWG)
Applicable
Gauges mm
2
(AWG)
24, 0, FE M2
0.22 to 0.25
(1.95 to 2.21)
0.75 (18 AWG)
Stranded wire:
0.25 to 1.0
(24 to 17 AWG)
Solid wire:
0.25 to 1.5
(24 to 16 AWG)
0.5 (20 AWG)
0.25 to 0.5
(24 to 20 AWG)
Shielded twisted
pair, etc.
n
Ferrule-Type Wire Terminals
Yaskawa recommends using CRIMPFOX 6, a crimping tool manufactured by PHOENIX CONTACT, to prepare wire ends
with insulated sleeves. See Table 3.27 for dimensions.
d1
d2
6 mm
L
(0.24 in.)
Figure 3.59 Ferrule Dimensions
Table 3.27 Ferrule Terminal Types and Sizes
Size mm
2
(AWG)
Type L mm (in) d1 mm (in) d2 mm (in) Manufacturer
0.25 (24)
AI 0.25-6YE
AI 0.25-6BU
10.5 (0.41) 0.8 (0.03) 2.0 (0.08)
PHOENIX CONTACT
0.34 (22) AI 0.34-6TQ 10.5 (0.41) 0.8 (0.03) 2.0 (0.08)
0.5 (20) AI 0.5-6WH 12 (0.47) 1.1 (0.04) 2.5 (0.10)
3.13 24 V Control Power Supply Unit Wiring
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
127
3
Electrical Installation