Setting Function Page
8 During Baseblock (N.O.) 291
9 Frequency Reference Source 291
A Run Command Source 291
B Torque Detection 1 (N.O.) 292
C Frequency Reference Loss 292
E Fault 292
F Through Mode 292
10 Minor Fault 292
11 Fault Reset Command Active 292
12 Timer Output 292
13 Speed Agree 2 292
14 User-Set Speed Agree 2 293
15 Frequency Detection 3 293
16 Frequency Detection 4 294
17 Torque Detection 1 (N.C.)
292
18 Torque Detection 2 (N.O.)
19 Torque Detection 2 (N.C.) 292
1A During Reverse 294
1B During Baseblock (N.C.) 295
1C Motor 2 Selection 295
1D During regeneration 295
1E Restart Enabled 295
1F Motor Overload Alarm (oL1) 295
20 Drive Overheat Pre-Alarm (oH) 295
22 Mechanical Weakening Detection 295
2F Maintenance Period 295
Setting Function Page
30 During Torque Limit 295
31 During Speed Limit 296
32 During Speed Limit in Torque Control 296
33 Zero Servo Complete 296
37 During Frequency Output 296
38 Drive Enabled 296
39 Power Consumption Pulse Output 296
3A Regenerated Power Pulse Output 296
3C LOCAL/REMOTE Status 296
3D During Speed Search 297
3E PID Feedback Low 297
3F PID Feedback High 297
4C During Fast Stop 297
4D oH Pre-Alarm Time Limit 297
60 Internal Cooling Fan Alarm 297
61 Rotor Position Detection Completed 297
62
MEMOBUS Register 1 (Selected with H2-07 and
H2-08)
297
63
MEMOBUS Register 2 (Selected with H2-09 and
H2-10)
297
64 During Commercial Power Operation 297
90 DriveWorksEZ Digital Output 1
29791 DriveWorksEZ Digital Output 2
92 DriveWorksEZ Digital Output 3
100 to 192 Functions 0 to 92 with Inverse Output 297
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Status Description
Open Drive is stopped.
Closed A Run command is input or the drive is in deceleration or DC injection.
ON
ON
OFF
OFF
ONOFF
Run command
Baseblock
command
Output
frequency
During Run
Figure 5.66 During Run Time Chart
Setting 1: Zero Speed
Terminal closes when the output frequency or motor speed (CLV, CLV/PM) becomes less than or equal to the minimum output
frequency set to E1-09 or b2-01.
5.7 H: Terminal Functions
288
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual