No.
(Addr.
Hex)
Name LCD Display Description Values Page
F6-54
(03C5)
DeviceNet Idle Mode
Fault Detection
DN Idle Flt Det
0: Stop
1: Ignore
All Modes
0: Enabled
1: Disabled, no fault detection
Default: 0
Range: 0, 1
275
F6-55
(03C6)
DeviceNet Baud Rate
Monitor
DN BAUD RATE
MEM
0: 125 kbps
1: 250 kbps
2: 500 kbps
All Modes
Verifies the baud rate running on the network.
0: 125 kbps
1: 250 kbps
2: 500 kbps
Default: 0
Range: 0 to 2
275
F6-56
(03D7)
DeviceNet Speed
Scaling
Speed Scale
All Modes
Sets the scaling factor for the speed monitor in DeviceNet.
Default: 0
Min.: -15
Max.: 15
275
F6-57
(03D8)
DeviceNet Current
Scaling
Current Scale
All Modes
Sets the scaling factor for the output current monitor in
DeviceNet.
Default: 0
Min.: -15
Max.: 15
275
F6-58
(03D9)
DeviceNet Torque
Scaling
Torque Scale
All Modes
Sets the scaling factor for the torque monitor in DeviceNet.
Default: 0
Min.: -15
Max.: 15
275
F6-59
(03DA)
DeviceNet Power
Scaling
Power Scale
All Modes
Sets the scaling factor for the power monitor in DeviceNet.
Default: 0
Min.: -15
Max.: 15
275
F6-60
(03DB)
DeviceNet Voltage
Scaling
Voltage Scale
All Modes
Sets the scaling factor for the voltage monitor in DeviceNet.
Default: 0
Min.: -15
Max.: 15
275
F6-61
(03DC)
DeviceNet Time Scaling Time Scale
All Modes
Sets the scaling factor for the time monitor in DeviceNet.
Default: 0
Min.: -15
Max.: 15
275
F6-62
(03DD)
DeviceNet Heartbeat
Interval
DN Heart Beat
All Modes
Sets the heartbeat interval for DeviceNet communications.
Default: 0
Min.: 0
Max.: 10
276
F6-63
(03DE)
DeviceNet Network
MAC ID
DN MAC ID MEM
All Modes
Saves and monitors settings 0 to 63 of F6-50 (DeviceNet MAC
Address).
Default: 63
Min.: 0
Max.: 63
276
F6-64 to
F6-71
(03DF to
03C8)
Reserved
All Modes
Reserved for Dynamic I/O Assembly Parameters.
F6-72
(03DE)
PowerLink Node
Address
PowerLink NodeID
All Modes
Reserved.
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Values shown are for the MECHATROLINK-II option (SI-T3). Values for MECHATROLINK-III option (SI-ET3) are:
Min: 03
Max.: EF
<3> Values shown are for the MECHATROLINK-II option (SI-T3). Values for MECHATROLINK-III option (SI-ET3) are:
0: 64-byte
1: 32-byte
B.8 F: Option Settings
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
529
B
Parameter List

Table of Contents