Table B.12 400 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
No. Name Unit Default Settings
Drive Model
4o0011 4o0014 4o0021 4o0027
C6-01 Drive Duty Selection HD ND HD ND HD ND HD ND
o2-04 Drive Model Selection Hex. 95 97 99 9A
E2-11
(E4-11)
Motor Rated Output
kW
(HP)
3.7 (5) 5.5 (7.5) 5.5 (7.5) 7.5 (10) 7.5 (10) 11 (15) 11 (15) 15 (20)
b3-04 V/f Gain during Speed Search % 100 100 100 100 100 100 100 100
b3-06 Output Current 1 during Speed Search 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b8-03 Energy Saving Control Filter Time Constant s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
b8-04 Energy Saving Coefficient Value 313.6 245.8 245.8 189.5 189.5 145.38 145.38 140.88
C5-17 (C5-37) Motor Inertia
kgm
2
0.0088 0.0158 0.0158 0.0255 0.026 0.037 0.037 0.053
C6-02 Carrier Frequency Selection 1 1 1 1 1 1 1 1
E2-01 (E4-01) Motor Rated Current A 4.2 7 7 9.8 9.8 13.3 13.3 19.9
E2-02 (E4-02) Motor Rated Slip Hz 3 2.7 2.7 1.5 1.5 1.3 1.3 1.7
E2-03 (E4-03) Motor No-Load Current A 1.5 2.3 2.3 2.6 2.6 4 4 5.6
E2-05 (E4-05) Motor Line-to-Line Resistance Ω 6.495 3.333 3.333 1.595 1.595 1.152 1.152 0.922
E2-06 (E4-06) Motor Leakage Inductance % 18.7 19.3 19.3 18.2 18.2 15.5 15.5 19.6
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 77 130 130 193 193 263 263 385
E5-01 Motor Code Selection (for PM Motors) Hex. 1236 1236 1238 1238 123A 123A 123B 123B
L2-02 Momentary Power Loss Ride-Thru Time s 0.5 0.6 0.6 0.7 0.7 0.8 0.8 0.9
L2-03
Momentary Power Loss Minimum
Baseblock Time
s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
L2-04
Momentary Power Loss Voltage Recovery
Time
s 300 300 300 300 300 300 300 300
L2-21 Low Input Voltage Detection Level V 300 300 300 300 300 300 300 300
L8-02 Overheat Alarm Level °C 130 130 130 130 130 130 130 130
L8-35 Installation Method Selection 0 0 0 0 0 0 0 0
L8-38 Carrier Frequency Reduction Selection 1 1 1 1 1 1 1 1
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10 10
n5-02 Motor Acceleration Time s 0.145 0.154 0.154 0.168 0.168 0.175 0.175 0.265
Table B.13 400 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
No. Name Unit Default Settings
Drive Model
4o0034 4o0040 4o0052 4o0065
C6-01 Drive Duty Selection HD ND HD ND HD ND HD ND
o2-04 Drive Model Selection Hex. 9C 9D 9E 9F
E2-11
(E4-11)
Motor Rated Output
kW
(HP)
15 (20) 18.5 (25) 18.5 (25) 22 (30) 22 (30) 30 (40) 30 (40) 37 (50)
b3-04 V/f Gain during Speed Search % 100 100 100 100 100 100 100 100
b3-06 Output Current 1 during Speed Search 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b8-03 Energy Saving Control Filter Time Constant s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
b8-04 Energy Saving Coefficient Value 140.88 126.26 126.26 115.74 115.74 103.58 103.58 92.54
C5-17 (C5-37) Motor Inertia
kgm
2
0.053 0.076 0.076 0.138 0.138 0.165 0.165 0.220
C6-02 Carrier Frequency Selection 1 1 1 1 1 1 1 1
E2-01 (E4-01) Motor Rated Current A 19.9 26.5 26.5 32.9 32.9 38.6 38.6 52.3
E2-02 (E4-02) Motor Rated Slip Hz 1.7 1.6 1.6 1.67 1.67 1.7 1.7 1.8
E2-03 (E4-03) Motor No-Load Current A 5.6 7.6 7.6 7.8 7.8 9.2 9.2 10.9
E2-05 (E4-05) Motor Line-to-Line Resistance Ω 0.922 0.55 0.55 0.403 0.403 0.316 0.316 0.269
E2-06 (E4-06) Motor Leakage Inductance % 19.6 17.2 17.2 20.1 20.1 23.5 23.5 20.7
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 385 440 440 508 508 586 586 750
B.18 Defaults by Drive Model and Duty Rating ND/HD