Table B.15 400 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
No. Name Unit Default Settings
Drive Model
4o0180 4o0216 4o0240 4o0302
C6-01 Drive Duty Selection HD ND HD ND HD ND HD ND
o2-04 Drive Model Selection Hex. A5 A6 A7 A8
E2-11
(E4-11)
Motor Rated Output
kW
(HP)
90 (125)
110
(150)
110
(150)
132
(175)
132
(175)
150
(200)
150
(200)
185
(250)
b3-04 V/f Gain during Speed Search % 60 60 60 60 60 60 60 60
b3-06 Output Current 1 during Speed Search 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
b8-03 Energy Saving Control Filter Time Constant s 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00
b8-04 Energy Saving Coefficient Value 46.2 38.91 38.91 36.23 36.23 32.79 32.79 30.13
C5-17 (C5-37) Motor Inertia
kgm
2
0.900 1.100 1.10 1.90 1.90 2.10 2.10 3.30
C6-02 Carrier Frequency Selection 1 1 1 1 1 1 1 1
E2-01 (E4-01) Motor Rated Current A 130 156 156 190 190 223 223 270
E2-02 (E4-02) Motor Rated Slip Hz 1.39 1.4 1.4 1.4 1.4 1.38 1.38 1.35
E2-03 (E4-03) Motor No-Load Current A 36 40 40 49 49 58 58 70
E2-05 (E4-05) Motor Line-to-Line Resistance Ω 0.092 0.056 0.056 0.046 0.046 0.035 0.035 0.029
E2-06 (E4-06) Motor Leakage Inductance % 20 20 20 20 20 20 20 20
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 1600 1760 1760 2150 2150 2350 2350 2850
E5-01 Motor Code Selection (for PM Motors) Hex. 1246 1246 1247 1247 1248 1248 1249 1249
L2-02 Momentary Power Loss Ride-Thru Time s 1.3 1.5 1.5 1.7 1.7 1.7 1.7 1.8
L2-03
Momentary Power Loss Minimum
Baseblock Time
s 1 1 1 1 1 1 1 1
L2-04
Momentary Power Loss Voltage Recovery
Time
s 300 300 300 300 300 300 300 300
L2-21 Low Input Voltage Detection Level V 300 300 300 300 300 300 300 300
L8-02 Overheat Alarm Level °C 130 130 130 130 130 130 130 130
L8-35 Installation Method Selection 0 0 0 0 0 0 0 0
L8-38 Carrier Frequency Reduction Selection 1 1 1 1 1 1 1 1
n1-03 Hunting Prevention Time Constant ms 30 30 30 30 30 30 30 30
n5-02 Motor Acceleration Time s 0.533 0.592 0.592 0.646 0.646 0.673 0.673 0.777
Table B.16 400 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
No. Name Unit Default Settings
Drive Model
4o0361 4o0414 4o0477 4o0590
C6-01 Drive Duty Selection HD ND HD ND HD ND HD ND
o2-04 Drive Model Selection Hex. A9 AA AC AD
E2-11
(E4-11)
Motor Rated Output
kW
(HP)
185
(250)
220
(300)
220
(300)
260
(350)
260
(350)
300
(400)
300
(400)
375
(500)
b3-04 V/f Gain during Speed Search % 60 60 60 60 60 60 60 60
b3-06 Output Current 1 during Speed Search 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
b8-03 Energy Saving Control Filter Time Constant s 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00
b8-04 Energy Saving Coefficient Value 30.13 30.57 30.57 27.13 27.13 21.76 21.76 21.76
C5-17 (C5-37) Motor Inertia
kgm
2
3.30 3.60 3.60 4.10 4.10 6.50 6.50 11.00
C6-02 Carrier Frequency Selection 1 1 1 1 0 0 0 0
E2-01 (E4-01) Motor Rated Current A 270 310 310 370 370 500 500 500
E2-02 (E4-02) Motor Rated Slip Hz 1.35 1.3 1.3 1.3 1.3 1.25 1.25 1.25
E2-03 (E4-03) Motor No-Load Current A 70 81 81 96 96 130 130 130
E2-05 (E4-05) Motor Line-to-Line Resistance Ω 0.029 0.025 0.025 0.02 0.02 0.014 0.014 0.014
E2-06 (E4-06) Motor Leakage Inductance % 20 20 20 20 20 20 20 20
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 2850 3200 3200 3700 3700 4700 4700 4700
B.18 Defaults by Drive Model and Duty Rating ND/HD
592
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual