No. Name Unit Default Settings
– Drive Model –
4o0361 4o0414 4o0477 4o0590
C6-01 Drive Duty Selection – HD ND HD ND HD ND HD ND
o2-04 Drive Model Selection Hex. A9 AA AC AD
E2-11
(E4-11)
Motor Rated Output
kW
(HP)
185
(250)
220
(300)
220
(300)
260
(350)
260
(350)
300
(400)
300
(400)
375
(500)
E5-01 Motor Code Selection (for PM Motors) Hex. 124A 124A FFFF FFFF FFFF FFFF FFFF FFFF
L2-02 Momentary Power Loss Ride-Thru Time s 1.8 1.9 1.9 2 2 2.1 2.1 2.1
L2-03
Momentary Power Loss Minimum
Baseblock Time
s 1 1 1 1 1.8 2.0 2.0 2.0
L2-04
Momentary Power Loss Voltage Recovery
Time
s 300 300 300 300 300 300 300 300
L2-21 Low Input Voltage Detection Level V 300 300 300 300 300 300 300 300
L8-02 Overheat Alarm Level °C 130 130 130 130 130 130 130 130
L8-35 Installation Method Selection – 0 0 0 0 0 0 0 0
L8-38 Carrier Frequency Reduction Selection – 1 1 1 1 1 1 1 1
n1-03 Hunting Prevention Time Constant ms 30 30 100 100 100 100 100 100
n5-02 Motor Acceleration Time s 0.777 0.864 0.864 0.91 0.91 1.392 1.392 1.392
Table B.17 400 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
No. Name Unit Default Settings
– Drive Model –
4o0720 4o0900 4o0930
C6-01 Drive Duty Selection – HD ND HD ND HD ND
o2-04 Drive Model Selection Hex. AE AF B0
E2-11 (E4-11) Motor Rated Output
kW
(HP)
300 (400) 375 (500) 375 (500) 450 (600) 450 (600) 500
b3-04 V/f Gain during Speed Search % 60 60 60 60 60 60
b3-06 Output Current 1 during Speed Search – 0.7 0.7 0.7 0.7 0.7 0.7
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
– 0.8 0.8 0.8 0.8 0.8 0.8
b8-03 Energy Saving Control Filter Time Constant s 2 2 2 2 2 2
b8-04 Energy Saving Coefficient Value – 21.76 23.84 23.84 21.4 21.4 20.26
C5-17 (C5-37) Motor Inertia
kgm
2
11 12 12 13 13 14
C6-02 Carrier Frequency Selection – 0 0 0 0 0 0
E2-01 (E4-01) Motor Rated Current A 500 650 650 800 800 900
E2-02 (E4-02) Motor Rated Slip Hz 1.25 1 1 1 1 0.9
E2-03 (E4-03) Motor No-Load Current A 130 130 130 160 160 180
E2-05 (E4-05) Motor Line-to-Line Resistance Ω 0.014 0.012 12.000 mΩ 10.000 mΩ 10.000 mΩ 9.000 mΩ
E2-06 (E4-06) Motor Leakage Inductance % 20 20 20 20 20 20
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 4700 5560 5560 7060 7060 7833
E5-01 Motor Code Selection (for PM Motors) Hex. FFFF FFFF FFFF FFFF FFFF FFFF
L2-02 Momentary Power Loss Ride-Thru Time s 2.1 2.3 2.3 2.8 2.8 3.1
L2-03 Momentary Power Loss Minimum Baseblock Time s 2 2.2 2.2 2.6 2.6 3
L2-04 Momentary Power Loss Voltage Recovery Time s 300 300 300 300 300 300
L2-21 Low Input Voltage Detection Level V 300 300 300 300 300 300
L8-02 Overheat Alarm Level °C 135 135 135 135 135 135
L8-35 Installation Method Selection – 0 0 0 0 0 0
L8-38 Carrier Frequency Reduction Selection – 1 1 1 1 1 1
n1-03 Hunting Prevention Time Constant ms 100 100 100 100 100 100
n5-02 Motor Acceleration Time s 1.392 1.667 1.667 2 2 2.222
B.18 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
593
B
Parameter List