Loading...
n
Single Drive Installation
Figure 2.2 and Figure 2.3 show the installation distance required to maintain sufficient space for airflow and wiring.
Drive Models 2o0028 to 2o0248 and 4o0011 to 4o0590
A
C
A
B
B
D
E
Side Clearance Top/Bottom Clearance
A 50 mm (1.97 in) minimum
B 30 mm (1.18 in) minimum
C 200 mm (7.87 in) minimum
D 120 mm (4.72 in) minimum
E Airflow direction
Figure 2.2 Correct Drive Installation Spacing
Note: IP20/UL Type 1 enclosure and IP00/Open Type enclosure models require the same amount of space above and below the drive for
installation.
Drive Models 4o0720 to 4o0930 and Harmonic Filter Module
Side Clearance Top/Bottom Clearance
A
A
C
B
B
E
D
F
Drive Model
Harmonic
Filter Module
4o0720
A 50 mm (1.97 in) minimum
B 30 mm (1.18 in) minimum
C 200 mm (7.87 in) minimum
D 120 mm (4.72 in) minimum
E 60 mm (2.36 in) minimum
F Airflow direction
Figure 2.3 Correct Drive Model 4o0720 and Harmonic Filter Module Installation Spacing
2.2 Mechanical Installation
60