WARNING! Electrical Shock Hazard. Because the leakage current exceeds 3.5 mA in models 4
o
0302 and larger, IEC/EN
61800-5-1 states that either the power supply must be automatically disconnected in case of discontinuity of the protective earthing
conductor, or a protective earthing conductor with a cross-section of at least 10 mm
2
(Cu) or 16 mm
2
(Al) must be used. Failure to
comply may result in death or serious injury.
C
B
A
A Braided shield cable
B Metal panel
C Cable clamp (conductive)
Figure D.5 Ground Area
IM
U/T1
W/T2
W/T3
R/L1
S/L2
T/L3
PE
ELCB
(MCCB)
EMC filter Drive
Three-phase
power supply
Motor
Ground
shielded line main circuit terminal
control circuit terminal
Figure D.6 Wiring Diagram for EMC (Models 4o0477 and 4o0590)
D.2 European Standards
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
653
D
Standards Compliance