<6. PARAMETER DESCRIPTION>
6-7
IM 01E30D01-01EN
(5) Item E (Menu E): Pulse Setting items
Menu E contains items relevant to pulse output. This is used to set parameters such as the pulse scale and
width.
Item
Name
R/W
Data range
Units
Position
of decimal
point
Default value
(*): Indicated item
Description
Display unit
(BRAIN)
Display unit
/BRAIN
E00 Pulse Set
(PULSE SET)
E10 Pulse Unit
(PULSE UNIT)
W n Unit/P
u Unit/P
m Unit/P
Unit/P
k Unit/P
M Unit/P
Pulse/s
Pulse/s (*) Selectstheowrateunitper
one pulse as used for pulse
output. Linked with B32.
E11 Pulse Scale
(PULSE SCALE)
W 0 to 32000 E10
(B32)
0 to 4 0 (*) Setstheowrateperone
pulse as used for pulse output.
Linked with B33.
E12 Pulse Width
(PULSE WIDTH)
W 50% Duty
0.05 ms
0.1 ms
0.5 ms
1 ms
20 ms
33 ms
50 ms
100 ms
200 ms
330 ms
500 ms
1000 ms
2000 ms
50% Duty Selects the pulse width for
pulse output.
E13 Pulse Low Cut
(PULSE LOWCUT)
W 0 to 100 % 0 3 % Sets the range in vicinity of 0%
within which pulse output will
be halted.
E14 Pulse Rate Check
(PLS RATE CHK)
R 0 to 999999 Pulse/s 0 to 5 0.0 Displays the pulse output rate
in “Pulse/s”
E60
(SELF CHECK)
R Good
Error
Read Section 6.5 “Alarm
Functions”.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA ADMAG AXR and is the answer not in the manual?

YOKOGAWA ADMAG AXR Specifications

General IconGeneral
BrandYOKOGAWA
ModelADMAG AXR
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals