4-3
Pioneer Gold 3.00 Controller Technical Guide
SCREENS
Setpoints
Setpoint Values
Refer to the following for setpoint names and their min/max
and defaults.
Cooling Setpoints
• Occupied Cooling: Sets the Cooling Setpoint. Default:
• Unoccupied Cooling: Sets the Unoccupied Cooling
• Cooling Enable Deadband: How far away from
Range: 1-5°F
• Supply Air Cooling Setpoint:
Range: 45-65°F
Heating Setpoints
• Occupied Heating: Sets the Heating Setpoint.
• Unoccupied Heating: Sets the Unoccupied Heating
• Heating Enable Deadband: How far away from the
Range: 1-5°F
• Supply Air Heating Setpoint:
Range: 55-120°F
• Auxiliary Heat Deadband: Space Temp has to be this
far below setpoint before Aux Heat can energize.
Setpoints
MAIN MENU
CO2GlycolCompressor
Supply
Fan
EconDehumHeatCool
MAIN MENU
CO2GlycolCompressor
Supply
Fan
EconDehumHeatCool
Occupied Cooling
Unoccupied Cooling
Supply Air Cooling
Cool Enable Deadband 1ºF
55ºF
80ºF
74ºF
Space Hi Reset
Space Lo Reset
Supply Hi Reset
Supply Lo Reset 53ºF
57ºF
72ºF
75ºF
Cooling Setpoints
MAIN MENU
Occupied Heating
Unoccupied Heating
Supply Air Heating
Heat Enable Deadband 1ºF
90ºF
65ºF
70ºF
Space Hi Reset
Space Lo Reset
Supply Hi Reset
Supply Lo Reset 90ºF
100ºF
69ºF
72ºF
Heating Setpoints Page 1
NEXT
NEXT
MAIN MENU
MAIN MENU
Setpoints
Setpoints
Aux Heat Deadband
5ºF
Heating Setpoints Page 2
MAIN MENU
MAIN MENU
Setpoints
Setpoints
BACK
BACK
Figure 4-5: Setpoints - Menu
Figure 4-6: Setpoints - Cooling
Figure 4-7: Setpoints - Heating