Section 5 TLL Displays Timer Display
3BUR002418-600 A 113
The following fields can be edited on this display:
Time entries can be made in the following formats:
One colon preceded by one or two digits means minutes and seconds.
Examples:
30:05 30 minutes 5 seconds
12:40 12 minutes 40 seconds
One colon preceded by three digits means hours and minutes.
Example:
010:15 10 hours 15 minutes
Two colons indicate hours and minutes.
Examples:
8:07: 8 hours, 7 minutes
12:16:10.2 12 hours, 16 minutes, 10.2 seconds
Preset
Value
The Preset and Value fields are displayed to the hundredth
place. For example, 001:20:15.25 is one hour, twenty
minutes, fifteen and twenty-five hundredths seconds. Your
entry should be within the resolution of the time base. If it is
not, the system automatically rounds it to the nearest
multiple of the time base. You can change the preset or
value of a timer by selecting the Preset or Value field for the
timer, entering the new value, then pressing ENTER. The
changes are logged.
Enable This field is used to enable and disable the timer. You can
change between YES (enable) and NO (disable) by
selecting the Enable field for the timer, clicking on the
appropriate Enable button, then pressing ENTER. The
changes are logged.
Description Use this field to modify the associated description.