Appendix A Runtime Templates Absolute Value FCM
3BUR002418-600 A 259
Constant 1 Field
This field specifies the values of the constant. Valid entry is any number
Absolute Value FCM
The Absolute Value FCM calculates the absolute value of the input signal.
Scale Compensation Calculator FCMs
This section describes the active runtime fields on the following scale compensation
calculator FCM templets. See Common Calculator FCM Fields on page 256 for
common fields.
Modified Square Root
Linearization
Normalize
Inverse Normalize
•Scale Input
Flow Calculation
Temperature Compensation
Ratio/Bias
Modified Square Root FCM
The Modified Square Root FCM calculates the square root of its input for input
values greater than 2.47% of range. For input values less than 2.47%, including
negative input values, the result is modified to be linear near zero and to handle
negative numbers. The Modified Square Root FCM extracts the square root and
scales the percent value into engineering units.
HI ENG UNITS Field (High Engineering Units)
This field specifies the high limit of the engineering units range. Valid entry is any
number.