Viewing Alarms on MOD Loop Displays Section 8 Operation Examples
208 3BUR002418-600 A
configured for automatic mode only. This ensures that all mode transfers and
manual intervention can be accomplished exclusively at the slave.
Viewing Alarms on MOD Loop Displays
Alarms can be configured for each control loop to respond to an alarm condition on
the process variable, the control output, and the deviation between the setpoint and
process value (as a normalized measured value into the PID FCM). Alarm types can
be high, high high, low, low low or limit alarms. The parameters of these alarms can
be adjusted during operation on the loop detail display.