MOD Group Displays Section 3 CCF Displays
62 3BUR002418-600 A
MOD Group Displays
A group is a collection of related loops. Generally, a group has up to 12 control
loops or up to 36 indicator loops or a combination of both. Control loops assigned to
indicator targets provide limited information and cannot be used for control.
Monitoring and control functions (control is enabled in the MOD Group Object) are
provided in the Group Status and Group Trend displays. A custom graphic can be
configured for the Group Graphic display. The Group Alarm display is a filtered list
of a selected event group page.
Group Status Display
The Group Status Display, Figure 18, shows the current status of all tags within the
group by organizing the tags into status blocks (one per control loop, and up to three
indicator loops). Trend data is shown for PID and A/M control loops which have
trending configured in the database. Device loop status blocks show tag, descriptor,
command state, mode, and state. Indicator loop status blocks show basic
information for up to three tags.