Appendix A Runtime Templates Adaptive Gain
3BUR002418-600 A 245
Alarm PRIORITY Fields
These following fields specify the priority levels for their respective alarms.
• OUTPUT HIGH PRIORITY
• OUTPUT LOW PRIORITY
• OUTPUT RATE PRIORITY
• BAD OUTPUT PRIORITY
• SETPOINT HIGH PRIORITY
• SETPOINT LOW PRIORITY
• BAD SETPT PRIORITY
• DEVN HIGH PRIORITY
• DEVN LOW PRIORITY
Valid entries are:
STD standard priority
MED medium priority
HIGH high priority
Adaptive Gain
The PID Controller FCM uses adaptive gain and/or adaptive reset to adapt to
changing process conditions. This templet is a child of the PID Controller FCM
Templet.
HIGH LIMIT Field
The field specifies the overall high limit for gain or reset when any adaptive function
is used. Valid entry is a decimal value.
LOW LIMIT Field
This field specifies the overall low limit for gain or reset when any adaptive function
is used. Valid entry is a decimal value.