ABB 800xA - Ai820

ABB 800xA
332 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AI820 Appendix A Runtime Templates
286 3BUR002418-600 A
The default range is 0..20mA.
REPORT FAULTS 01 through 08
If channel faults are to be reported, enter a YES; if not enter a NO.
The default value is YES.
RESERVED OPTIONS
Used to select I/O module type:
Enter:
0 (zero) for the AI810 Module
274333696 for the AI890 Module
The default value is 0 (zero).
VALUE CYCLE TIME
Enter the channel value update period (msec) over the fieldbus. Refer to the S800
I/O User’s Guide for details of AF 100 loading in relation to cycle time.
The valid values are:
1, 2, 4, 8, 16, 32, 64, 128, 256, 512, 1024, 2048 and 4096.
The default value is 128.
AI820
S800 I/O AI820 Differential Analog Input Module Templet.
ACTIVE 01 through 04
If the channel is to be active enter a YES.
If the channel will not be used enter a NO.
The default value is YES.