Appendix A Runtime Templates AI820
3BUR002418-600 A 287
AUTO DOWNLOAD
To automatically download the configuration to the I/O module enter a YES. In the
future, if the configuration is to be loaded locally enter a NO.
Default value is YES.
CLUSTER
Enter the I/O device cluster of the station where this module is located. The cluster
connected directly to the FCI is number zero (0). The number in this field is 0 -7.
Default value is 0.
DEAD BAND 01 through 04
Enter the difference in successive signal count values before a new value will be
sent.
The valid values are:
NONE, 0, 1, 3, 7, 15, 31, 63, 127, 255, 511, 1023, 2047, 4095, 8191 and 16383.
The default value is NONE.
FILTER TIME 01 through 04
Enter the lowpass filter time constant (msec) for each channel.
The possible range is:
20 to 65535.
The default value is 20 (20msec).
LABEL
Enter a characteristic name to identify the AI820 Module of the station. The name
may contain up to 20 characters.
LINEARIZATION 01 through 04
If a channel needs to apply the square-root-law linearization, enter a YES;
if not enter a NO.