Appendix A Runtime Templates DI810
3BUR002418-600 A 301
DI810
The DI810 templet is also used for the DI890 except as noted in the field entry
descriptions. The DI890 also supports only 8 channels.
ACTIVE 01 through 16
If the channel is to be active enter a YES.
If the channel will not be used enter a NO.
The default value is YES.
AUTO DOWNLOAD
To automatically download the configuration to the I/O module enter a YES. In the
future, if the configuration is to be loaded locally enter a NO.
Default value is YES.
CLUSTER
Enter the I/O device cluster of the station where this module is located. The cluster
connected directly to the FCI is number zero (0). The number in this field is 0 -7.
Default value is 0.
FILTER
Enter the input filter time in msec.
The valid values are:
2, 4, 8 and 16.
The default value is 2.