Appendix A Runtime Templates AI810, AI890
3BUR002418-600 A 285
LABEL
Enter a characteristic name to identify the AI810 or AI890 Module of the station.
The name may contain up to 20 characters.
LINEARIZATION 01 through 08
If the channel needs to apply the square-root-law linearization, enter a YES; if not
enter a NO.
The default is NO.
POSITION
Enter a number from 1 to 12 representing the position of the I/O module relative to
the FCI. The first I/O module directly next to the FCI is number 1.
Default value is 1.
POWER LINE FREQUENCY
Enter the power line frequency to filter out (notch) the signal.
The valid values are:
16, 50, and 60.
The default value is 60.
RANGE 01 through 08
The valid values are:
0..10V (not valid for AI890)
0..20mA
For the AI890 module, enter a description that includes the module type for
future reference to help alleviate confusion with an AI890 being used in the
AI810 templet.
If positions are to be used for spare MTUs, the spares must be in place so the rest
of the I/O modules are numbered correctly. The spare MTU will use a position
number when it is on the ModuleBus.