Adaptive Gain Appendix A Runtime Templates
246 3BUR002418-600 A
CONTACT STATE Field
This field specifies on which state of the contacts the gain or reset is adapted by the
contact adaptive function.
Valid entries are:
TRUE apply the contact adaptive function when the signal is true (closed
contacts - non-zero)
FALSE apply the contact adaptive function when the signal is false (open
contacts - zero)
CONTACT GAIN Field
This field specifies the factor by which the base gain or reset is multiplied when the
contact adaptive function is applied. Valid entry is a decimal value.
REMOTE HIGH LIMIT Field
This field specifies the maximum allowed value for the remote variable adaptive
contribution to the overall gain or reset. Valid entry is a decimal number.
REMOTE LOW LIMIT Field
This field specifies the minimum allowed value for the remote variable adaptive
contribution to the overall gain or reset. Valid entry is a decimal number.
REMOTE UPPER BRKPT Field
This field specifies the upper breakpoint, BP2, for the remote variable adaptive
function. The gain or reset changes when the remote variable becomes greater than
the upper breakpoint.
Valid entry is a decimal value with the same type of units as the remote variable
(eng. units or percent).