Section 7 I/O Displays S800 Station Display
3BUR002418-600 A 153
The top of the S800 Station display identifies the I/O Station, its Advant Controller
and has other information as described below.
Devsub The controller DCN address where the S800 I/O is located.
State This field shows the status of the controller as ACTIVE, DOWN or
AVAIL.
Name The controller subsystem part of the logical name created during
database configuration.
Lan This field represents the number of the Local Area Network (LAN)
for all the stations shown. For the AC 460 this is LAN # 1 - 4 and
for the AC 410 this is LAN # 1 or 2.
Go back to the controller display to select a different LAN.
Station This field represents the number of the station.
Go back to the LAN display to select a different station.
Templet The logical device name created during database configuration is
given in this field.
Label Descriptive label associated with templet.
RPT Faults Indicates the reporting method for fault condition. FLASH NOTIFY,
SILENT NOTIFY or NO NOTIFY.
Media This shows the status of the AF 100 bus media.
NONE means that no bus is connected.
BOTH means that dual media is used and that both are
operational.
CABLE 1 UP or CABLE 2 UP shows if only one bus is
connected and operational.