Appendix A Runtime Templates Loop Definition Templet
3BUR002418-600 A 215
LO ENG. UNIT LIMIT Field
Specifies the lower boundary for the trend graphs. Valid entries are: a decimal
number.
HI ENG. UNIT LIMIT Field
Specifies the upper boundary for the trend graphs. Valid entries are: a decimal
number.
MEASUREMENT UNITS Field
Specifies engineering units labels. The labels are used when the measured variable
of the loop is displayed on operational displays. Valid entry is: any string of up to 6
alphanumeric characters, for example, GPM, PSIG
LOOP STATE Field
This field determines whether the loop is processed. When LOOP STATE is OFF,
the loop processor ignores the loop. Valid entries are: ON (process the loop), OFF
(do not process the loop).
SUPPRESS ALARMS Field
This field determines if the loop processor checks that alarms defined by this loop
are active. Valid entries are: YES (suppress alarms - do not check), NO (do not
suppress alarms).
ENABLE POSTING Field
This field specifies whether posting is enabled for the loop. Posting affects the way
alarm information is presented. Valid entries are: YES (enable posting), NO (disable
posting).