Valid entries are:
YES enable
NO disable
REVERT COMMAND Field
This field specifies the command to which DEV_CMND is automatically set as part
of revert.
Valid entry is:
a command from the descriptor set defined for the device on its Device
Descriptor Templet
CUTOUT ENABLE Field
This field specifies whether cutout is enabled for the loop. Cutout allows an FCM of
this or another loop to control the posting of the alarms.
Valid entry is:
YES enable the cutout feature
NO disable the cutout feature
OUTPUT ERROR ACTION Field
This field specifies the actions taken when the output driver fails.
Valid entries are:
NOTHING continue normal processing
GOTO BACKUP processing goes to the Backup Controller Module if one is
present. This option shuts down CCF processing in a
Multibus subsystem when the driver fails.
LOOP OFF turn the loop off