Appendix A Runtime Templates PID Controller FCM
3BUR002418-600 A 233
PROCESS HIGH VALUE Field
This field gives the value of the process input corresponding to 100.0% of the range.
Valid entry is a decimal value.
PROCESS LOW VALUE Field
This field gives the value of the process input corresponding to 0.0% of the range.
Valid entry is a decimal value.
INITIAL MODE Field
This field specifies the output mode at start-up time. Valid entries are:
MAN - start in the Manual mode
AUTO - start in the Auto mode
INITIAL OUTPUT Field
This field specifies the value of the output at startup time. Valid entry is a value in
percent.
INITIAL SETPOINT Field
This field indicates the value of the setpoint at start-up time. Valid entry is a value
scaled in engineering units
INITIAL SETPT MODE Field
This field specifies the setpoint mode at start-up time. Valid entries are:
LOC - local setpoint mode
REM - remote setpoint mode
LIMITED SETPT MODES Field
This field specifies the setpoint modes to which the setpoint limits are applied. Valid
entries are: NONE, LOC, TRK, REM, RMP, TRK/REM, TRK/RMP, REM/RMP,