PID Controller FCM Appendix A Runtime Templates
236 3BUR002418-600 A
BAD INPUTS ACCEPTED Field
This field specifies whether an input with BAD data quality is treated as if the data
quality is GOOD. Valid entries are:
NO do not accept bad inputs
YES accept bad inputs
ACTION ON BAD INPUT Field
This field specifies the action to take if the controller input signal goes to BAD data
quality. Valid entries are:
FCM OFF controller FCM is turned off
MAN OUT controller FCM goes to the Manual output mode
NONE FCM continues processing according to its configuration
ACTION ON BAD SETPT Field
This field specifies the action to take if the setpoint signal goes to a BAD data
quality. Valid entries are:
NONE no special action is taken
MAN OUT output mode is switched to Manual
LOC SPT setpoint mode goes to Local
FCM OFF FCM is turned off
SETPOINT RETURN MODE Field
This field specifies the setpoint mode to enter when the mode returns from Track.
Valid entries are:
PREVIOUS go to the mode active before the setpoint went to Track
LOCAL go to the Local mode
REMOTE go to the Remote mode